Choose a relay socket for a DIN rail panel by matching the exact relay first-not by matching only the number of pins. Confirm the relay manufacturer, complete part number, pin geometry, terminal map, contact form and approved socket list. Then check the whole installed interface: current path, coil-side electronics, conductor and terminal limits, DIN rail profile, temperature derating, touch protection, approvals, accessories and service space.
The fastest safe selection rule
Freeze one exact relay order code. Obtain the manufacturer's compatible socket and accessory list. Reject any candidate that cannot provide a matching pin diagram, model-specific ratings, conductor data, rail details, temperature limits and approval conditions. A socket that accepts the relay mechanically can still be electrically wrong.
This guide is for control-panel designers, electrical engineers, machine builders, system integrators, panel shops, maintenance teams, distributors and sourcing engineers. It covers general-purpose and interposing electromechanical relays used in industrial panels. Safety relays, hazardous-location systems, railway, medical and other high-consequence applications need additional application-specific requirements.
![]()
A plug-in relay and its base form one serviceable interface, but mechanical fit alone does not prove correct pin mapping or electrical ratings. Image: Balurbala, Wikimedia Commons, CC BY-SA 3.0.
Use Eight Selection Gates Before Approving a Socket
A practical review should move from compatibility to installation evidence. If a candidate fails an early gate, do not spend time comparing convenience features.
| Selection gate | Evidence required | Reject when |
|---|---|---|
| 1. Exact compatibility | Approved relay-to-socket table and full order codes | Only pin count, appearance or a verbal "universal" claim is available |
| 2. Terminal mapping | Top/bottom-view drawing with A1, A2, COM, NO and NC labels | The view direction or terminal allocation is ambiguous |
| 3. Electrical path | Relay, socket, terminal, wire, jumper and protection ratings | One part of the path is below the required load or lacks conditions |
| 4. Coil interface | Voltage, AC/DC type, polarity and accessory circuit | LED, diode, rectifier or suppressor identity is unknown |
| 5. Wiring process | Conductor, ferrule, strip length, wire count, torque and tools | The panel shop cannot build the connection as documented |
| 6. Mechanical system | Rail profile, clip, end stops, envelope and extraction space | The socket merely "seems to clip" onto the available rail |
| 7. Thermal and safety | Derating, temperature test, insulation, IP and approvals | Ratings lack ambient, loading or certification conditions |
| 8. Controlled release | Sample results, BOM, drawings, accessories and alternate rules | Purchasing can substitute a visually similar base without review |
Understand What the Relay Socket Controls
A DIN rail relay socket-also called a relay base-is the removable interface between a plug-in relay and panel wiring. Internal conductors route the relay coil and contacts to accessible terminals, while the housing provides insulation, rail mounting, labeling and mechanical support. The socket therefore affects electrical performance, wiring labor, temperature rise, maintenance and compliance.
| Interface element | Function | Common omission |
|---|---|---|
| Plug-in relay | Coil, mechanism and switching contacts | Selecting from contact amperes without load-life data |
| Socket/base | Pin interface, panel terminals, insulation and mounting | Treating it as a passive plastic holder |
| Retention/ejector clip | Prevents walk-out or assists removal | Leaving the correct clip out of the BOM |
| Indicator/protection module | Adds LED, diode, RC, varistor or rectification | Ignoring voltage, polarity and release-time effects |
| Jumper/bridge | Distributes a common potential across a row | Letting a lower-rated jumper become the hot spot |
| Marker, separator and end stop | Identification, segregation and rail restraint | Treating them as installation-shop extras |
IEC 60715 defines dimensional and functional requirements for compatible mounting on standardized rails. It also states that any protective-earthing function of the rail belongs to the relevant product standard. A metal rail beneath a socket is not automatically a verified protective conductor.
Exact Relay Compatibility Comes Before Pin Count
Start with the relay's complete order code. Family suffixes can change coil voltage, AC/DC construction, indicator, test button, contact material, pin allocation, approval or housing. Record the approved socket, holding clip and accessory module for that exact suffix before considering alternates.
| Compatibility check | Compare | Failure if assumed |
|---|---|---|
| Pin geometry | Blade/round form, width, thickness, length, pitch, keying and insertion depth | Loose fit, bent pins or the wrong internal conductor |
| Contact form | SPDT, DPDT, 3PDT, 4PDT, NO-only, NC-only or special form | Same pin count but different coil/contact allocation |
| Terminal map | A1/A2, COM, NO, NC, pole numbers and drawing view | Mirrored wiring or energized wrong contact |
| Mechanical envelope | Relay body, clip groove, test button and installed height | Interference with clip, duct, cover or cabinet door |
| Combination approval | Relay and socket records plus conditions of use | A relay mark is incorrectly applied to an unlisted base |
Are 8-pin, 11-pin and 14-pin sockets universal?
No. Those labels count connection points; they do not define the pitch, keying, pin shape, terminal numbering, coil location, body fit or ratings. Even when a relay inserts without force, the terminals may connect to different functions. Use the manufacturer compatibility table and dimensioned terminal drawing as purchasing evidence.
Drawing-control rule: put the socket part number, diagram view direction and functional terminal labels on the schematic and wire list. Never ask an assembler to mentally rotate an unlabeled "8-pin socket diagram" at the panel.
Size the Complete Current Path by Its Weakest Component
The allowed current is the lowest applicable limit among the relay contacts under the real load, socket conductors, terminals, wire, jumper, protective device, ambient-temperature derating and any total multipole condition. The relay's switching capacity may be lower again because electrical life depends on load type, voltage, inrush and operating frequency.
| Published value | What it establishes | What it cannot establish |
|---|---|---|
| Socket carry/thermal current | Continuous current for the stated model and conditions | Relay make/break capacity, inrush endurance or electrical life |
| Relay resistive-load rating | Contact capability for one defined load condition | Motor, solenoid, lamp, transformer, capacitor or all DC loads |
| Operational voltage | Intended operating voltage of a named component path | Switching capability, impulse withstand or every insulation barrier |
| Jumper rating | Current permitted through the specified bridge and positions | Every socket terminal or an unlimited daisy chain |
| Wire range | Permitted conductor types and sizes under stated preparation | Any ferrule, two-wire combination or torque |
| SCCR | Short-circuit treatment under defined component/assembly rules | Continuous current; it cannot be inferred from 6 A, 10 A or hi-pot data |
Model-specific examples show why labels are incomplete
Schneider Electric's RXZE2S111M data sheet lists 10 A conventional free-air thermal current for the socket but 5 A with its specified bus jumper. OMRON's current Push-In Plus data shows 10 A at 55°C and 7 A at 70°C for certain models, while other socket models use different values and total-current conditions. These are examples of the method-not universal limits. Copy the exact conditions for the selected order code.
AC and DC switching are also different. A DC arc has no natural current-zero crossing, so a relay may interrupt much less DC current than its familiar AC resistive rating. Separate the current a closed path can carry from the current the contacts can repeatedly make and break. Verify voltage, load type, inrush, duty cycle, frequency, suppression and life together.
Check the Coil Side and Every Plug-In Module
A passive socket only routes the coil pins. A socket or plug-in module containing an LED, diode, bridge rectifier, RC network, varistor or other circuit has its own voltage, frequency and polarity requirements. Once electronics are present, the base is no longer interchangeable merely because the relay pins fit.
| Coil-side feature | Verify | Mismatch risk |
|---|---|---|
| LED indicator | Voltage range, AC/DC type, polarity, leakage and meaning | Dim glow, false diagnosis or overheating |
| Freewheeling diode | A1/A2 polarity, controller protection and release time | Shorted output, no operation or slow drop-out |
| Zener/TVS/varistor | Clamp voltage, energy, polarity, EMC and release speed | Inadequate protection or excessive stress |
| RC network | Voltage, frequency, leakage, residual voltage and heat | Relay fails to release or controller behaves unexpectedly |
| Bridge rectifier | Documented AC/DC input range and compatible relay | Wrong coil voltage or excess dissipation |
| Manual test control | Momentary/lockable behavior and maintenance policy | Unexpected machine movement or unsafe testing |
PLC transistor and triac outputs, indicator circuits and cable capacitance can pass off-state leakage current. In low-power interfaces this can cause a dim LED, residual voltage, chatter, delayed release or failure to drop out. Measure voltage and current at the assembled socket under worst-case field conditions; do not decide from the PLC status bit alone.
Do not add a bleeder resistor or suppressor from habit. It changes dissipation, fault behavior, safety spacing and controller loading. Calculate the circuit, verify component limits and test pickup/dropout at voltage and temperature extremes.
Choose the Terminal Technology for the Actual Wiring Process
| Terminal type | Useful when | Control point |
|---|---|---|
| Screw / box clamp | Mixed maintenance teams, field rewiring or broad conductor use | Torque, tool access, strand containment and approved wire count |
| Spring-cage | Vibration, flexible wiring and repeated servicing | Operating tool, insertion method, conductor and ferrule limits |
| Direct push-in | High-volume builds with standardized solid or ferruled wire | Strip length, ferrule geometry, release tool and pull inspection |
| Plug-in connector | Prebuilt harnesses and modular machine sections | Coding, retention, mating cycles and another current-carrying interface |
Terminal technology changes the conductor preparation, tooling, access and inspection plan. Copy the connection data from the exact socket rather than from a similar terminal family. Image: Dmitry G, Wikimedia Commons, CC BY-SA 3.0.
The wiring specification should name conductor material, solid or flexible construction, cross-section or AWG, ferrule type, collar acceptance, strip length, conductors per terminal, torque and tools. A range stated for one conductor does not approve two conductors or a twin ferrule. Do not tin stranded wire before clamping unless the manufacturer explicitly permits it; solder can creep under pressure and reduce connection force.
Model-specific example: Phoenix Contact lists an 8 mm strip length, M3 screw, defined rigid/flexible/ferrule ranges and 0.6–0.8 N·m torque for PLC-BSC-12DC/21-21. Those numbers do not transfer to another socket, even within the same brand.
Confirm the DIN Rail, Retention and Service Envelope
"DIN rail" names a standardized mounting family, not one guaranteed profile. Confirm the exact type and depth stated in the socket data, such as a 35 mm symmetrical rail or a named NS 35/7.5 profile. Check rail material, thickness, finish, fixing intervals, mounting orientation and whether panel screw mounting is also permitted.
Rail width alone is not the complete mechanical specification. Profile, depth, material, thickness and the socket's approved clip all affect engagement. Image: Dmitry G, Wikimedia Commons, public-domain release.
| Mechanical item | Verify | Panel consequence |
|---|---|---|
| Rail profile | Profile, depth, material, thickness, finish and approved rail | Clip engagement, stiffness and installation repeatability |
| End stops | Approved type, tightening method and transport loads | Prevents the row from sliding and stressing wires/jumpers |
| Mounting orientation | Any-position approval or required orientation | Retention, convection, labels and manual-test access |
| Holding clip | Exact relay groove, material and removal method | Prevents vibration walk-out without blocking service |
| Installed envelope | Socket width, relay height, module, clip, jumper and wire bend | Rail length, duct spacing and door clearance |
| Tool/extraction path | Screwdriver angle, release tool, probe and straight pull-out path | A CAD-fit part can still be impossible to wire or replace |
Calculate row length from actual pitch, end stops, separators, spare ways and accessory overhang. Check depth from mounting plate to the highest relay or clip, including door devices and harness movement. Reserve enough vertical space to insert wires and remove the relay without dismantling the wire duct. A narrow socket can save rail width but increase service labor if access is poor.
Apply Temperature and Dense-Mounting Derating
A relay row produces coil heat plus I²R losses in contacts, pins, socket conductors, terminals, jumpers and wires. The enclosure temperature may be much higher than the room temperature, especially beside drives, power supplies, contactors or transformers.
Use the manufacturer's definition of ambient and every derating curve. A zero-spacing mounting statement applies only to the exact product and stated conditions; it does not prove that a fully loaded row meets the panel's temperature-rise or service-life objective.
| Thermal input | Worst case to test | Release evidence |
|---|---|---|
| Enclosure ambient | Maximum internal air temperature and ventilation state | Thermal model and measured stabilized temperature |
| Simultaneous loading | Maximum credible energized coils and contact poles | Duty/load matrix and current measurements |
| Common jumper | Sum current at the most heavily loaded bridge segment | Jumper map, rating and temperature rise |
| Neighbors | Adjacent heat sources, ducting and cabinet solar load | Representative panel layout and thermography |
| Service aging | Insertion/removal and retermination after realistic use | Resistance, retention and inspection records |
Measure terminals, socket body, relay, jumper, adjacent wires and nearby components after thermal equilibrium. Investigate discoloration, odor, softened plastic, unstable contact resistance or chatter. Set an engineering limit below component maximums to protect wire insulation, relay life and neighboring equipment.
Review Insulation, Touch Protection, Environment and Standards
| Review item | Question | Boundary |
|---|---|---|
| Operational voltage | Maximum normal voltage at every coil/contact terminal? | Not automatically a switching or transient rating |
| Creepage/clearance | Does the complete installed assembly meet the product requirement? | Socket geometry cannot approve the whole panel |
| Dielectric/impulse data | Which barrier, voltage, waveform, duration and conditioning? | A test value cannot be moved to an undefined path |
| Pollution/environment | Dust, condensation, oil, salt or corrosive gas at the base? | Enclosure rating and internal microenvironment are not identical |
| IP/touch protection | Are live parts protected after approved wires and jumpers are fitted? | IP20 on one component does not approve the wired panel |
| Shock/vibration | Were socket, relay, clip, rail and conductors tested together? | A secure rail hook does not prevent relay walk-out |
Component standards and certificates support the review but do not replace it. IEC 61984 addresses connector safety requirements and tests; IEC 61810-1 covers general and safety requirements for electromechanical elementary relays. IEC 61439-1 provides general rules for low-voltage assemblies and must be used with the relevant part of the series. For North American industrial control panels, the responsible panel team must verify component treatment, certification records and conditions under the current UL 508A framework.
Do not infer SCCR from a socket ampere rating
A 10 A socket label does not mean 10 kA-or any other short-circuit current rating. SCCR depends on specific component and assembly rules, protective devices, available fault current and conditions of use. If the interface lies in a circuit relevant to the panel SCCR, document how the exact component is treated. Never manufacture an SCCR value from carry current, fuse size or dielectric withstand.
Control Accessories as Part of the Interface BOM
| Accessory | Why it matters | Control in the BOM |
|---|---|---|
| Hold-down clip | Maintains engagement under vibration or aids ejection | Exact material/part number and relay housing compatibility |
| Protection module | Controls coil transient and EMC behavior | Voltage, AC/DC, polarity, energy and release-time effect |
| Indicator module | Shows control voltage for troubleshooting | Range, color, polarity, leakage, power and diagnostic meaning |
| Bus jumper | Reduces repetitive common wiring | Current, pitch, pole count, position and maximum chain |
| Marker/separator | Supports identification and segregation | Approved system, durable text and any claimed insulation role |
| Rail end stop | Prevents row movement during wiring and transport | Rail compatibility, quantity, position and tightening method |
Treat relay, socket, clip, module, jumper, marker, separator, rail and end stops as one controlled interface system. This prevents a purchasing substitution from silently changing polarity, current, panel width, retention or labeling. Stock service spares as compatible sets when field identification is difficult.
Follow a Twelve-Step Relay Socket Selection Workflow
| Step | Action | Release evidence |
|---|---|---|
| 1 | Define circuit function, load, failure consequence, duty, environment and standards | Application specification and schematic |
| 2 | Freeze the exact relay family, suffix, coil and contact requirements | Current relay datasheet and order code |
| 3 | Obtain the official compatible socket and accessory list | Compatibility table or written confirmation |
| 4 | Compare pin geometry and the view-specific terminal map | Dimensioned drawing and annotated wiring diagram |
| 5 | Calculate load path, inrush, DC interruption, poles, jumpers and protection | Load profile and current-path calculation |
| 6 | Confirm coil voltage, AC/DC, polarity, electronics, leakage and release time | Driver calculation and bench-test plan |
| 7 | Approve conductor, ferrule, strip length, wire count, torque and tools | Wiring specification and work instruction |
| 8 | Confirm rail, orientation, restraint, dimensions and service access | Panel layout and access review |
| 9 | Apply temperature, row, pole and jumper derating | Worst-case thermal limits |
| 10 | Verify insulation, IP, environment, approvals and panel treatment | Compliance matrix and certificate review |
| 11 | Build representative samples in the real rail, enclosure, wire and load | Fit, pull, functional, thermal and abnormal-test records |
| 12 | Release BOM, drawings, labels, spares, alternates and PCN rules | Signed design record and supplier control plan |
Apply the Workflow to Real Panel Scenarios
PLC output driving a 24 V DC solenoid
Confirm the exact relay and approved base. If the interface includes a suppression diode, document A1/A2 polarity and compare PLC off-state leakage with the relay release data. Check the suppression method's effect on drop-out time. On the contact side, verify solenoid inrush, DC switching rating, operating frequency, expected life and load suppression; then validate the full socket/wire/jumper path at the highest panel temperature.
Dense interposing-relay row for alarm channels
A slim push-in or spring-cage system can reduce wiring time and improve channel labeling. Size the common-coil bridge from the sum of simultaneously energized coils, not one channel. Consider whether one failed common or fuse can disable multiple alarms; segment the row when the required availability demands it. Test a representative full row thermally.
Four-pole relay switching several circuits
Several loaded poles concentrate coil heat and current in one base. Check any total-current condition, pole-to-pole insulation and whether different voltages, phases or safety domains are permitted. Multiple schematic poles are not automatically multiple independently approved safety barriers.
Safety-related functions
Do not use a general-purpose relay and socket as a safety relay system merely because the relay has several contacts. Safety functions may require force-guided contacts, monitoring architecture, diagnostic coverage, fault exclusions, a verified performance level or SIL and approved components. Define the safety function first, then use the specified module, base and wiring architecture.
Approve Samples Before Releasing the BOM
| Sample check | Method | Accept when |
|---|---|---|
| Identity | Record relay, socket, suffix, lot, markings, accessories and certificates | Every item matches approved documentation |
| Mechanical fit | Insert/remove relay and fit clips, jumpers, markers, rail and stops | Positive engagement with no bent pins, looseness or interference |
| Terminal map | Continuity-test A1/A2 and every COM/NO/NC path | Physical product matches the published view and wire list |
| Conductor/torque | Use minimum/maximum approved wire, ferrule, strip length and tools | No exposed copper, loose strands, damage or abnormal resistance |
| Coil behavior | Test tolerance, polarity, LED, leakage, pickup, dropout and release | Interface works with the real controller in all states |
| Thermal/load | Operate the worst credible row and load until stable | All temperatures and behavior stay within controlled limits |
| Service/vibration | Apply required shock/vibration and replacement cycles | Relay, clip, rail hook, terminals and markers remain secure |
Electrical safety: de-energize, isolate, lock out and verify absence of voltage before installing, rewiring, removing or inspecting a relay/socket. A PLC-off command, open contact, manual test button or dark LED is not proof of isolation.
Troubleshoot Socket Problems from the Interface Outward
| Symptom | Check first | Corrective direction |
|---|---|---|
| Relay will not energize | A1/A2 voltage under load, polarity, exact maps, seating and terminal continuity | Correct BOM/wiring and replace damaged parts |
| Slow or failed release | PLC leakage, residual voltage, diode/RC network and release time | Use a calculated, validated interface design |
| Hot socket/terminal | Current map, jumper, simultaneous poles, ambient, wire and torque | De-energize, correct cause and replace heat-damaged mating parts |
| Intermittent output | Bent/dirty pins, worn contacts, cracked terminal, vibration and clip | Replace mating pair as needed and improve retention/environment |
| Wrong contact switches | Top/bottom-view confusion, pinout, labels and jumper position | Correct documents/wiring and block incompatible alternates |
| Difficult relay removal | Extraction space, clip, deformation and incompatible pins | Redesign service access or replace damaged components |
| Discoloration or odor | Overload, arcing, termination, chemical attack and protection | Remove from service and complete root-cause analysis |
Relay Socket RFQ and Purchase Specification
- Relay identity: manufacturer, family, full part number, coil, contact form, pin geometry and approved base.
- Electrical load: AC/DC voltage, steady current, inrush, load type, duty, switching frequency, life objective and suppression.
- Socket path: carry current, operational voltage, total multipole condition, jumper rating and temperature derating.
- Coil interface: controller output, coil voltage/frequency, polarity, leakage, LED, diode/TVS/RC/rectifier and release-time target.
- Terminations: conductor material/type, mm²/AWG, ferrule, wires per terminal, strip length, torque and approved tools.
- Mechanical: DIN rail profile, orientation, socket width/depth/height, clip, end stop, duct clearance and extraction path.
- Environment: internal panel ambient, humidity, condensation, dust, oil, corrosive gas, altitude, shock and vibration.
- Safety/compliance: applicable panel/equipment standards, voltage/insulation data, IP, flammability, approvals, file numbers and conditions.
- Accessories: exact jumper, marker, separator, module, holding clip, rail and end-stop part numbers.
- Quality and supply: factory, traceability, sample report, lifecycle, PCN period, MOQ, lead time, spares and approved alternates.
For a useful QIANJI model review: send the exact relay code, coil voltage, contact load, wire/ferrule, rail profile, panel ambient, required standards/approvals and accessory list. The goal is to review one complete compatible interface-not to match an "8-pin socket" from appearance alone.
Frequently Asked Questions
Can a relay socket carry the relay's full rated current?
Only when every installed-path limit permits it. Compare relay switching/carry data with socket, terminal, conductor, jumper, multipole total, ambient derating and protective-device conditions. The lowest applicable limit controls.
What DIN rail size is normally used for relay sockets?
Many industrial sockets specify a 35 mm symmetrical rail, sometimes a named NS 35/7.5 profile, but "35 mm" does not define every depth, material or geometry. Use the exact socket data and approved rail specification.
Is push-in better than a screw-terminal relay socket?
Neither is universally better. Push-in can reduce assembly time with standardized conductors. Screw terminals are familiar but need controlled torque and access. Spring-cage designs can suit vibration and flexible wire. Choose from the factory process, conductor, tools, inspection and maintenance plan.
Can an AC relay use a socket sold for a DC relay?
A passive base may support listed AC and DC relay variants, but a base with an LED, diode, rectifier or suppressor has its own input identity. Verify the exact combination. Never apply AC to a diode-only DC interface or assume "AC/DC" without documentation.
Do I need a relay hold-down clip?
Use the specified clip when required by the manufacturer, approval configuration or shock/vibration conditions. Verify that the exact clip fits the relay groove and does not obstruct labels, test controls, adjacent modules or safe removal.
Can a plug-in relay be removed while energized?
Plug-in construction is not permission for live removal. Exposed terminals can carry hazardous voltage, and removal can arc or unexpectedly switch machinery. Follow the approved isolation, lockout/tagout and absence-of-voltage procedure unless a specifically engineered live-work method applies.
Does IP20 mean the wired socket is touch-safe?
Not automatically. Wire preparation, exposed strands, jumpers, test openings, covers and adjacent devices affect the completed assembly. Inspect the fully wired installation against the panel and equipment requirements.
How many relay sockets can be mounted side by side?
There is no universal number. Follow the exact model's mounting and derating instructions, then evaluate energized coils/poles, jumper current, enclosure temperature, ventilation, neighboring heat sources and service space. Validate a worst-case row thermally.
Final Relay Socket Selection Checklist
- The exact relay order code and manufacturer-approved socket are frozen.
- Pin geometry, contact form and top/bottom-view terminal map match.
- The relay, socket, wire, terminal, jumper and protective device have been checked as one current path.
- Coil voltage, AC/DC type, polarity, LED/suppressor and PLC leakage are documented.
- The conductor, ferrule, strip length, wire count, torque and tools are approved.
- The rail profile, orientation, end stops, clip and full service envelope fit the panel.
- Temperature derating and simultaneous row loading are validated in the enclosure.
- Insulation, touch protection, environment, approvals and panel-standard treatment are recorded.
- All modules, jumpers, markers, separators and spares have exact part numbers.
- Representative samples passed fit, continuity, functional, thermal and service checks.
- The controlled BOM defines approved alternates and supplier change notification.
Need a compatible relay-and-socket set for a DIN rail panel?
Send QIANJI the relay code, coil voltage, load, conductor, rail, panel temperature, target approvals and accessory requirements for model-level review and sample planning.
You can also review QIANJI's current relay socket range. Approve only the exact relay, socket and accessory combination supported by current drawings, ratings, samples and the required certification path.
Technical References
- IEC 60715:2017 - standardized mounting on rails
- IEC 61439-1:2020 - general rules for low-voltage assemblies
- IEC 61984:2008/COR1:2011 - connector safety requirements and tests
- IEC 61810-1:2015+AMD1:2019 - electromechanical elementary relays
- UL Solutions - current UL 508A component requirements resource
- OMRON - Push-In Plus relay socket data and compatibility
- Schneider Electric RXZE2S111M - model-specific socket and jumper ratings
- Phoenix Contact PLC-BSC-12DC/21-21 - model-specific coil, conductor, rail and temperature data
This article supports selection and validation; it is not an approval decision or live-work procedure. Product data, compatible part numbers, approvals and standards can change. Verify the current exact relay, socket, accessories, conductors, certificates, conditions of use, panel environment, fault current, protective device and end-use standard before release.